Kicked 90° Conduit Bend Calculator
A kicked 90° combines a 90° stub with an angled kick to elevate the run into a panel knockout or box. Enter stub height, kick height, trade size, and kick angle.
Kicked 90° Bend Multiplier & EMT Take-Up Chart
Subtract bender take-up to mark your 90° stub, then multiply kick height by the kick angle multiplier to mark from the back of the 90°:
| Kick Angle | Multiplier | Shrink / Inch | 4" Kick Mark (from Back of 90°) |
|---|---|---|---|
| 10° | 6.0 | 1/16" | 24" |
| 15° | 3.9 | 1/8" | 15 5/8" |
| 22.5° | 2.6 | 3/16" | 10 3/8" |
| 30° (Standard) | 2.0 | 1/4" | 8" |
| 45° | 1.4 | 3/8" | 5 5/8" |
Standard Hand-Bender EMT Take-Up: 1/2" EMT = 5" · 3/4" EMT = 6" · 1" EMT = 8". Stub Mark = Target Stub Height − Take-Up.
Use Conduit Bend Calc 100% offline on the jobsite
Frequently Asked Questions
How do you calculate a kicked 90 conduit bend?
First mark the 90° stub at target stub height minus bender take-up (5" for 1/2" EMT, 6" for 3/4" EMT, 8" for 1" EMT) and bend the 90°. Then measure from the back of the 90° by kick height × angle multiplier (2.0 at 30°) to place the kick mark and bend to your chosen kick angle.
Where do you measure the kick mark on a kicked 90?
Measure from the back of the finished 90° bend along the straight run toward the kick. For example, a 4" kick at 30° (multiplier 2.0) places the kick mark 8" from the back of the 90°.
What kick angle is best for a kicked 90?
30° is the standard choice when space allows because its 2.0 multiplier is fast to lay out. Use 10°, 15°, or 22.5° for shallow kicks into panel knockouts so wire pulling stays easy, and use 45° only when space behind the 90° is tight.
How does stub take-up affect a kicked 90?
Your 90° stub still needs the bender take-up subtracted before bending — 5" for 1/2" EMT, 6" for 3/4" EMT, and 8" for 1" EMT. Adding a kick changes elevation along the run, while total gain (90° gain + kick gain) reduces the cut length needed.
Does this kicked 90 calculator work for EMT and Rigid conduit?
Yes. The kick distance multiplier works identically for EMT, IMC, and Rigid conduit. For 90° stub take-up, standard hand-bender EMT values (5", 6", 8") are built in; confirm take-up stamped on your Rigid or IMC bender shoe before marking.