NEC Wire Size Calculator

Find the minimum NEC Table 310.16 copper or aluminum wire gauge (14 AWG to 500 kcmil) from load amps, termination temperature rating, and 125% continuous load rules.

NEC 2023 Table 310.16 Conductor Ampacity Chart (Cu & Al)

Allowable ampacities for up to 3 current-carrying conductors in a raceway at 30°C ambient (125% rule applies to continuous loads ≥ 3 hr):

Wire SizeCopper 60°CCopper 75°CCopper 90°CAluminum 75°CNEC 240.4(D) Max OCPD
14 AWG15 A20 A25 A—15 A Cu
12 AWG20 A25 A30 A20 A20 A Cu / 15 A Al
10 AWG30 A35 A40 A30 A30 A Cu / 25 A Al
8 AWG40 A50 A55 A40 APer 310.16
6 AWG55 A65 A75 A50 APer 310.16
4 AWG70 A85 A95 A65 APer 310.16
2 AWG95 A115 A130 A90 APer 310.16
1/0 AWG125 A150 A170 A120 APer 310.16
3/0 AWG165 A200 A225 A155 APer 310.16
4/0 AWG195 A230 A260 A180 APer 310.16
500 kcmil320 A380 A430 A310 APer 310.16

NEC 110.14(C)(1): Circuits ≤100 A default to 60°C terminations unless listed for 75°C; circuits >100 A use 75°C.

Use Conduit Bend Calc 100% offline on the jobsite

Get Free Android App on Google Play

Frequently Asked Questions

How does NEC Table 310.16 determine wire size?

NEC Table 310.16 lists allowable ampacities for up to three current-carrying conductors in a raceway or cable at 30°C ambient temperature across 60°C, 75°C, and 90°C insulation columns. Select the smallest AWG or kcmil whose ampacity meets or exceeds your design load.

Should I use the 60°C, 75°C, or 90°C ampacity column?

Follow NEC 110.14(C)(1): circuits rated 100 A or less (14–1 AWG) default to the 60°C column unless equipment terminations are listed for 75°C, while circuits over 100 A use the 75°C column. The 90°C column (THHN/THWN-2) is used only as a starting point for derating adjustments.

What is the 125% continuous load rule in the NEC?

Under NEC 210.19(A)(1) and 215.2(A)(1), a continuous load operating at maximum current for 3 hours or more must be multiplied by 125% before sizing conductors and overcurrent protection. For example, a 16 A continuous load requires 20 A minimum ampacity (12 AWG Cu).

How do copper and aluminum wire sizes compare?

Aluminum has higher electrical resistance than copper, so aluminum conductors typically step up one or two trade sizes for the same ampacity. For example, a 100 A feeder at 75°C takes 3 AWG copper or 1 AWG aluminum, and building wire aluminum starts at 12 AWG.

How does NEC 240.4(D) affect 14, 12, and 10 AWG wire?

Even though 75°C and 90°C THHN ratings are higher, NEC 240.4(D) caps standard overcurrent protection at 15 A for 14 AWG copper, 20 A for 12 AWG copper (15 A Al), and 30 A for 10 AWG copper (25 A Al). This calculator automatically applies those small-conductor caps.