NEC Voltage Drop Calculator

Calculate single-phase and three-phase voltage drop in volts and percent using NEC Chapter 9 Table 8 resistance, verify 3% branch / 5% total limits, and find the minimum AWG.

NEC Chapter 9 Table 8 Conductor Resistance & Voltage Drop Formulas

DC resistance at 75°C (Ω per 1,000 ft) used to verify NEC 210.19(A) 3% branch / 5% total voltage drop limits:

Wire SizeCopper R (Ω / 1,000 ft)Aluminum R (Ω / 1,000 ft)Max 1φ 120V Run @ 15A (≤3%)
14 AWG3.140—38 ft (Cu)
12 AWG1.9803.25060 ft (Cu)
10 AWG1.2402.04096 ft (Cu)
8 AWG0.7781.280154 ft (Cu)
6 AWG0.4910.808244 ft (Cu)
4 AWG0.3080.508389 ft (Cu)
2 AWG0.1940.319618 ft (Cu)
1/0 AWG0.1220.201983 ft (Cu)

Formulas: Single-phase VD = (2 × L × I × R) ÷ 1,000 · Three-phase VD = (1.732 × L × I × R) ÷ 1,000, where L is one-way feet and I is load amps.

Use Conduit Bend Calc 100% offline on the jobsite

Get Free Android App on Google Play

Frequently Asked Questions

What is the NEC 3% and 5% voltage drop recommendation?

NEC 210.19(A) Informational Note recommends keeping voltage drop to 3% or less on branch circuits and 5% or less combined across the feeder and branch circuit. Staying within 3% prevents motor overheating, dimmed lights, and nuisance equipment trips.

What is the formula for single-phase vs three-phase voltage drop?

Using NEC Chapter 9 Table 8 DC resistance R (ohms per 1,000 ft): single-phase VD = (2 × L × I × R) ÷ 1,000, and three-phase VD = (1.732 × L × I × R) ÷ 1,000, where L is one-way run length in feet and I is load current in amps.

How do copper and aluminum affect voltage drop?

Copper has lower resistance (approximately K ≈ 12.9 Ω·cmil/ft) than aluminum (K ≈ 21.2 Ω·cmil/ft). For the same wire size, current, and run length, aluminum drops about 64% more voltage than copper, so long aluminum runs usually step up one or two wire sizes.

How do I upsize AWG to stay under 3% voltage drop?

If calculated voltage drop exceeds 3%, step up to the next larger wire gauge (lower AWG number or larger kcmil) until drop falls at or below 3%. This calculator automatically shows the smallest compliant copper or aluminum wire size when your run is over limit.

Do I enter one-way distance or total round-trip wire length?

Always enter the one-way distance from the panel or source to the load (in feet or meters). The single-phase factor (2) and three-phase factor (√3 ≈ 1.732) already account for the return path.