Rolling Offset Conduit Calculator
A rolling offset shifts conduit both vertically (rise) and sideways (roll) in one plane. Enter rise, roll, and bend angle to calculate true offset, mark spacing, rotation angle, and shrink.
Rolling Offset True Offset & Multiplier Quick Reference
Calculate true offset first with Pythagoras, then apply standard conduit offset multipliers and shrink per inch:
| Rise × Roll | True Offset √(Rise² + Roll²) | 30° Mark Spacing (×2.0) | 30° Shrink (1/4"/in) | 45° Mark Spacing (×1.4) |
|---|---|---|---|---|
| 3" × 4" | 5.0" | 10" | 1 1/4" | 7" |
| 6" × 8" | 10.0" | 20" | 2 1/2" | 14" |
| 8" × 8" | 11.31" | 22 5/8" | 2 13/16" | 15 7/8" |
| 9" × 12" | 15.0" | 30" | 3 3/4" | 21" |
Formulas: True Offset = √(Rise² + Roll²); Mark Spacing = True Offset × Multiplier; Rotation Angle = atan(Roll ÷ Rise).
Use Conduit Bend Calc 100% offline on the jobsite
Frequently Asked Questions
How do you calculate a rolling offset in conduit?
First find the true offset using the Pythagorean theorem: true offset = √(rise² + roll²). Then multiply the true offset by the multiplier for your bend angle (2.0 for 30°, 1.4 for 45°) to get mark spacing, and multiply true offset by shrink per inch to get total shrink.
What is the true offset for a 6 inch rise and 8 inch roll?
Using √(6² + 8²) = √(36 + 64) = 10" true offset. At a 30° bend angle (multiplier 2.0), place your two bend marks 20" apart and allow 2.5" of shrink (10" × 1/4" per inch).
How much does a rolling offset shrink?
Rolling offset shrink is based on the true offset, not just the rise or roll alone. Multiply true offset by the shrink per inch for your bend angle: 1/4" per inch at 30° or 3/8" per inch at 45°. Add shrink before cutting conduit.
Should I use 30° or 45° bends for a rolling offset?
Use 30° bends when you have room — the 2.0 multiplier keeps math easy, shrink moderate, and wire pulling smooth. Choose 45° (1.4 multiplier) when space is tight and you need shorter mark spacing, keeping NEC 360° total bend limits in mind.
Does this rolling offset calculator work for EMT and Rigid conduit?
Yes. The true offset, bender rotation angle, mark spacing, and shrink formulas apply to EMT, IMC, and Rigid (RMC) conduit. Sight the rotation angle accurately before making the first bend to prevent doglegs.