Conduit Bend Calc Open Calculator →

Why Your 1/2" EMT 90° Stub Lands Short (+ Take-Up Fix)

Every apprentice learns the rule on day one: subtract 5" take-up for a 1/2" EMT 90° stub-up. You need a 14-3/8" stub into a disconnect, mark at 9-3/8", pull 90°, stand it on the slab — and your tape reads 14-1/8" or 14-3/4". Here is why benders disagree and the 60-second scrap calibration that locks every stub to 1/16".

Worked example: 14-3/8" stub-up in 1/2" EMT

Target finished stub height H = 14-3/8" (14.375"), measured from the outside back of the 90° to the cut top of the vertical leg. With standard 5" take-up: Mark from End = 14-3/8" − 5" = 9-3/8".

EMT Trade SizeStandard Take-UpMark for 14-3/8" StubDatum
1/2" EMT5"9-3/8"Arrow
3/4" EMT6"8-3/8"Arrow
1" EMT8"6-3/8"Arrow
1/2" EMT 90° Stub-Up · Target 14-3/8" − 5" Take-Up = 9-3/8" Mark Floor / Back-of-90° Datum (Measure Here) Arrow Mark: 9-3/8" measured from top cut end 14-3/8" Back-of-90° 5" Take-Up 60-Second 12" Calibration 1. Mark 12" on scrap, bend 90° 2. Measure floor-to-top height (S) Actual Take-Up = S − 12" Ex: 17-3/8" − 12" = 5-3/8" → Mark 9"

Insert the 9-3/8" tail forward through the bender hook, align the arrow on the mark, and measure finished height from the flat floor slab.

Why Ideal, Klein, and Greenlee do not always match

Two benders both stamped “5" Take-Up” still have different shoe radii, and mechanical or electric benders change the reference datum from the arrow to the hook front edge:

Bender ModelConduitCenterline Radius (R)Take-Up / DeductReference Datum
Ideal 74-0261/2" EMT4-5/16" (4.3125")5"Arrow
Klein 516031/2" EMT4-5/8" (4.625")5"Arrow
Greenlee 555 (electric)1/2" EMT4-5/16" (4.3125")7"Hook front edge
Greenlee 1800 (mech.)1/2" Rigid2-5/8" (2.625")5-1/2" (min stub 6-1/2")Hook front edge

Klein 51603's centerline radius is 5/16" larger than Ideal 74-026's, so gain and back-to-back behavior differ. And mixing a hand-bender arrow deduct (5") with a Greenlee 555 hook deduct (7") puts you 2" off immediately.

The 60-second 12" scrap-pipe calibration check

  1. Mark 12" from the square-cut end on a scrap piece of 1/2" EMT (24"+ long).
  2. Put the arrow on 12", apply heavy heel pressure, and bend a dead-square 90° verified with a magnetic torpedo level (over-pull ~91°–92° for springback).
  3. Stand the bend on a flat concrete slab and measure floor-to-top back-of-90 height (S).
  4. Compute Actual Take-Up = S − 12". Example: if S = 17-3/8", your real take-up is 5-3/8" — so your 14-3/8" stub marks at 14-3/8" − 5-3/8" = 9".

Bonus gain & radius check: Cut scrap to exactly 24", bend a 90° in the middle, and measure legs A and B from the back of the 90° to each end. Exact 90° gain is G = A + B − 24", and real centerline radius is R = G ÷ 0.4292.

4-point rookie mistake check

Run any EMT or Rigid/IMC stub-up instantly — or use the guided 12" scrap calibration flow in our offline Android app.

Frequently asked questions

Where do I mark 1/2" EMT for a 14-3/8" 90-degree stub-up?

At 9-3/8" from the cut end on a standard 1/2" EMT hand bender (14-3/8" − 5" take-up = 9-3/8"). Feed the 9-3/8" tail through the hook and line the bender arrow directly on the mark.

Why does my 1/2" EMT 90-degree stub land 1/4" to 3/8" short?

Common causes are a worn gang-box shoe whose real take-up has drifted (e.g., 5-3/8" instead of 5"), insufficient foot pressure allowing the pipe to walk during the pull, or over-bending slightly past 90°. A 12" scrap test reveals your exact take-up in 60 seconds.

What is the difference between Ideal 74-026, Klein 51603, and Greenlee 555?

Ideal 74-026 (R = 4-5/16") and Klein 51603 (R = 4-5/8") both use a 5" arrow take-up for 1/2" EMT but have different bend radii. The electric Greenlee 555 uses a 7" deduct measured from the hook front edge, not an arrow.

How do I check a 90-degree stub height accurately on site?

Stand the bent conduit upright on a flat concrete slab so the horizontal leg rests flush, confirm the vertical leg is plumb at 90° with a torpedo level, and butt your tape flat on the floor beside the vertical leg to read straight to the top cut edge.